| Customization: | Available |
|---|---|
| Breaking Capacity: | Low Voltage Circuit Breakers |
| Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency


Tion | In(A) Rated current In(A) | The adjusting rage of commuting current | The Cutting Capacity For Rated Limit Short Circuit Lcu,The Cutting Capacity For Rated Work Short Circuit Lcs | The distance of arcs(mm) | |||
400/415V | 690V | ||||||
Icu(KA) | Ics(KA) | Icu(KA) | Ics(KA) | ||||
GV3M10 | 10A | 6-10A | 15 | 7.5 | 4 | 2 | 50 |
GV3M16 | 16A | 10-16A | 15 | 7.5 | 4 | 2 | 50 |
GV3M20 | 20A | 14-20A | 15 | 7.5 | 4 | 2 | 50 |
GV3M25 | 25A | 16-25A | 15 | 7.5 | 4 | 2 | 50 |
GV3M40 | 40A | 25-40A | 15 | 7.5 | 4 | 2 | 50 |
GV3M63 | 63A | 40-63A | 15 | 7.5 | 4 | 2 | 50 |
GV3M80 | 80A | 56-80A | 15 | 7.5 | 4 | 2 | 50 |
N Characteristic Of Breaker(GV2 Motor Circuit Breaker) When Every Phase Load Is In Balance | |||||||||
The Multiple Of Rated Current | Starting State | Stipulated Time | Due Result | The Temperature Of Ambient Air | |||||
1.05 | Cold State | T≥2H | No Disjounting | +20℃±2℃ | |||||
1.3 | Hot State (Rises Up To The Stipulated Currentafter Following The Test Of No 1) | T< 2H | Disjounting | ||||||
10 | Cold State | T< 2S | Disjounting | ||||||
The Action Characteristic Of Breaker(GV2 Motor Circuit Breaker) When Every Phase Load Is In Balance | |||||||||
The Multiple Of Rated Current | Starting State | Stipulated Time | Due Result | The Temperature Ofambient Air | |||||
Any Two Phases | The Third Phases | ||||||||
1 | 0.9 | Cold State | T≤2H | No Disjounting | +40℃±2℃ | ||||
1.15 | 0 | Hot State (Rises Up To The Stipulatedcurrent After Following The Test Of No 1) | T< 2H | Disjounting | |||||