| Customization: | Available |
|---|---|
| Breaking Capacity: | Low Voltage Circuit Breakers |
| Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency


Specification | In(A) Rated current In(A) | The adjusting rage of commuting current | The cutting capacity for rated limit short circuit lcu,the cutting capacity for rated work short circuit lcs | The distance of arcs(mm) | |||
400/415V | 690V | ||||||
Icu(KA) | Ics(KA) | Icu(KA) | Ics(KA) | ||||
GV3M10 | 10A | 6-10A | 15 | 7.5 | 4 | 2 | 50 |
GV3M16 | 16A | 10-16A | 15 | 7.5 | 4 | 2 | 50 |
GV3M20 | 20A | 14-20A | 15 | 7.5 | 4 | 2 | 50 |
GV3M25 | 25A | 16-25A | 15 | 7.5 | 4 | 2 | 50 |
GV3M40 | 40A | 25-40A | 15 | 7.5 | 4 | 2 | 50 |
GV3M63 | 63A | 40-63A | 15 | 7.5 | 4 | 2 | 50 |
GV3M80 | 80A | 56-80A | 15 | 7.5 | 4 | 2 | 50 |
The action characteristic of breaker(GV2 Motor circuit breaker) when every phase load is in balance | |||||||||
The multiple of rated current | Starting state | Stipulated time | Due result | The temperature of ambient air | |||||
1.05 | Cold state | t≥2h | No disjounting | +20℃±2℃ | |||||
1.3 | Hot state (rises up to the stipulated currentafter following the test of No 1) | t< 2h | Disjounting | ||||||
10 | Cold state | t< 2s | Disjounting | ||||||
The action characteristic of breaker(GV2 Motor circuit breaker) when every phase load is in balance | |||||||||
The multiple of rated current | Starting state | Stipulated time | Due result | The temperature ofambient air | |||||
Any two phases | The third phases | ||||||||
1 | 0.9 | Cold state | t≤2h | No disjounting | +40℃±2℃ | ||||
1.15 | 0 | Hot state (rises up to the stipulatedcurrent after following the test of No 1) | t< 2h | Disjounting | |||||