Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Specification | Rated Current In(A) | The Adjusting Rage Of Commuting Current | The Cutting Capacity For Rated Limit Short Circuit Lcu,The Cutting Capacity For Rated Work Short Circuit Lcs | ||||||
230/240V | 400/415V | 440V | 500V | ||||||
Icu(KA) | Ics(KA) | Icu(KA) | Ics(KA) | Icu(KA) | Ics(KA) | Icu(KA) | |||
GV2ME01C | 0.16 | 0.10-0.16 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
GV2ME02C | 0.25 | 0.16-0.25 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
GV2ME03C | 0.4 | 0.25-0.40 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
GV2ME04C | 0.63 | 0.40-0.63 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
GV2ME05C | 1 | 0.63-1.00 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
GV2ME06C | 1.6 | 1.00-1.60 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
GV2ME07C | 2.5 | 1.60-2.50 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
GV2ME08C | 4 | 2.50-4.00 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
GV2ME10C | 6.3 | 4.00-6.30 | 100 | 100 | 100 | 100 | 50 | 50 | 50 |
GV2ME14C | 10 | 6.00-10.00 | 100 | 100 | 100 | 100 | 15 | 15 | 10 |
GV2ME18C | 14 | 9.00-14.00 | 100 | 100 | 15 | 7.5 | 8 | 4 | 6 |
GV2ME20C | 18 | 13.00-18.00 | 100 | 100 | 15 | 7.5 | 8 | 4 | 6 |
GV2ME21C | 23 | 17.00-23.00 | 50 | 50 | 15 | 6 | 6 | 3 | 4 |
GV2ME22C | 25 | 20.00-25.00 | 50 | 50 | 15 | 6 | 6 | 3 | 4 |
GV2ME32C | 32 | 24.00-32.00 | 50 | 50 | 10 | 5 | 6 | 3 | 4 |
The Action Characteristic Of Breaker(GV2 Motor Circuit Breaker) When Every Phase Load Is In Balance | |||||||||
The Multiple Of Rated Current | Starting State | Stipulated Time | Due Result | The Temperature Of Ambient Air | |||||
1.05 | Cold State | T≤2H | No Disjounting | +40℃±2℃ | |||||
1.2 | Hot State (Rises Up To The Stipulated Currentafter Following The Test Of No 1) | T< 2H | Disjounting | ||||||
1.5 | One-Time Commuting Curren | T< 2Min | Disjounting | ||||||
Starts After The Bot Balance | |||||||||
7.2 | Cold State | 2<T≤10S | Disjounting |
The Action Characteristic Of Breaker(GV2 Motor Circuit Breaker) When Every Phase Load Is In Balance | |||||||||
The Multiple Of Rated Current | Starting State | Stipulated Time | Due Result | The Temperature Ofambient Air | |||||
Any Two Phases | The Third Phases | ||||||||
1 | 0.9 | Cold State | T≤2H | No Disjounting | +40℃±2℃ | ||||
1.15 | 0 | Hot State (Rises Up To The Stipulatedcurrent After Following The Test Of No 1) | T< 2H | Disjounting |